Installation - Controllers
90 UNT-SVX07J-EN
all WCIs having matching addresses automatically join the
network.
Wireless Zone Sensors
The WCI also communicates with Trane wireless zone
sensors, eliminating the need for analog receivers.
Wired Zone Sensors
Systems using WCI can also use wired zone sensors.
Specifications
Operating Temperature: -40 to 158ºF (-40 to 70ºC)
Storage temperature: -40 to 185ºF (-40 to 85°C)
Storage and operating humidity range: 5 percent to 95
percent relative humidity (RH), non-condensing
Voltage: 24 Vac/VDC nominal ± 10 percent. If using 24 Vac,
polarity must be maintained.
Receiver power consumption: <2.5 VA
Housing material: Polycarbonate/ABS (suitable for
plenum mounting), UV protected, UL 94: 5VA flammability
rating
Mounting: Snaps into sheet metal opening.
Range: Open range: 2,500 ft (762 m) with packet error rate
of 2 percent.
Indoor: Typical range is 200 ft (61 mm); actual range is
dependent on the environment. See BAS-SVX55-EN for
more detail.
Note: Range values are estimated transmission distances
for satisfactory operation. Actual distance is job
specific and must be determined during site
evaluation. Placement of WCI is critical to proper
system operation. In most general office space
installations, distance is not the limiting factor for
proper signal quality. Signal quality is affected by
walls, barriers, and general clutter. For more
information os available at www.trane.com.
Output power: North America: 100 mW
Radio frequency: 2.4 GHz (IEEE Std 802.15.4-2003
compliant) (2405–2480 MHz, 5 MHz spacing)
Radio channels: 16
Address range: Group 0–8, Network 1–9
Mounting
Fits a standard 2 in. by 4 in. junction box (vertical mount
only). Mounting holes are spaced 3.2 in. (83 mm) apart on
vertical center line. Includes mounting screws for junction
box or wall anchors for sheet-rock walls. Overall
dimensions: 2.9 in. (74 mm) by 4.7 in. (119 mm)
Wireless protocol
ZigBee PRO—ZigBee Building Automation Profile, ANSI/
ASHRAE Standard 135-2008 Addendum q (BACnet™/
ZigBee)

Table of Contents

Other manuals for Trane UniTrane

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane UniTrane and is the answer not in the manual?

Trane UniTrane Specifications

General IconGeneral
BrandTrane
ModelUniTrane
CategoryHeater
LanguageEnglish

Related product manuals