30 Wireless Sensors • BAS-SVX04C-EN
Operation
Star(*)/Double Star(**) Function
The star/double star function is available on models WDS and WZS. Consult the
appropriate unit controller documentation for information about this function.
The WZS sensor set supports star(*) and double star(**) on the sensor thumb wheel
(Figure 7).
• Star(*): A value of 95ºF (35ºC) is communicated.
• Double star(**): A value of 44.6ºF (7ºC) is communicated.
The WDS sensor set supports star(*) and double star(**) functions if the sensor is
configured for single setpoint operation. Press the up or down arrow on the keypad to
display the star(*) or double star(**), respectively, on the sensor display.
• If the setpoint is increased one increment above 89.6ºF (32ºC), the star (*) appears. A
value of 95ºF (35ºC) is communicated.
• If it is decreased one increment below 50ºF (10ºC), the double star(**) appears. A
value of 44.6ºF (7ºC) is communicated.
End-of-Range Temperature Values
Receiver: The end-of-range temperature limits of the receiver for all models are 32°F to
122°F (0°C to 50°C). The receiver cannot replicate temperature values outside this range.
If the sensor transmits a temperature value to the receiver that is out of the receiver
replication range, the receiver will “freeze” the output at the end-of-range values. This
value will remain frozen until the transmitted temperature moves to between the end-of-
range temperature limits.
Sensor: The end-of-range temperature setpoint limits for the model WDS sensor is 50°F
(10°C) to 89.6°F (32°C). The end-of-range temperature setpoint limits for the model WZS
sensor is 45°F (7.22°C) to 95°F (35°C).
Figure 7. WZS sensor: Thumb wheel
** on thumb wheel
(* is hidden from view)