BAS-SVX04C-EN • Wireless Sensors 19
Installation
Associating the Sensor to the Receiver
To associate the sensor to the receiver:
1. Remove the sensor cover by firmly pressing the thumb tab at the bottom of the cover
and pulling the cover away from the back plate.
2. Verify that the sensor is set to the same address as the receiver it is to be associated
with.
3. Power the sensor by removing the insulation strip from between the two batteries.
Association is automatically initiated between the sensor and the receiver. When LED3
on the receiver stops blinking, association has been established.
If the first association attempt is unsuccessful, the sensor automatically re-attempts
association with the receiver every 10 minutes.
Note: An associated sensor that has lost communication with the receiver will transmit
an association request every 50 minutes. You can manually initiate association
(see “Manual Association,” p. 41”).