EasyManuals Logo
Home>TSI Instruments>Controller>FHC50

TSI Instruments FHC50 User Manual

TSI Instruments FHC50
107 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
Appendix B
82
Description of LON SNVTs
SNVT
Command Supported
Action
nviEmergency:
EMERG_NORMAL
Sets NORMAL mode
EMERG_PURGE
Sets EMERGENCY mode
NOTE: All other commands set NORMAL mode
SNVT
Command Supported
Action
nviControlMode:
OC_OCCUPIED
Sets NORMAL mode
OC_STANDBY
OC_UNOCCUPIED
Sets SETBACK mode
Sets SETBACK mode
NOTE: All other commands set NORMAL mode
SNVT
Command Supported
Action
nviRequest
CLEAR_ALARM
Clears alarm (See SNVT nvoAlarm)
object_request
SNVT
Value Sent
Action
nviOverrideOn
x.x 1
x.x 0
Moves damper to override position
Exit Override mode
x.x is damper position between 0.0 to 100.0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TSI Instruments FHC50 and is the answer not in the manual?

TSI Instruments FHC50 Specifications

General IconGeneral
BrandTSI Instruments
ModelFHC50
CategoryController
LanguageEnglish

Related product manuals