Internet Alarm Communicator Installation Manual
Interval 2:
The module will send periodic test transmissions to secondary receivers (Ethernet secondary)
independently, with no backups.
If the test transmission fails to any of the programmed secondary receivers, an FTC trouble will
be generated.
[026] Ethernet 1 Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See system test options (above) for
details on settings.
[027] Ethernet 2 Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See system test options (above) for
details on settings.
[030] FTC Restore
Default (FF)
Program 00 to disable this event transmission or FF to enable. This event will occur when an FTC
Trouble on the system restores.
[037] System Firmware Update Fail
Default (FF);
Program 00 to disable this event transmission or FF to enable. This event will occur when the
panel firmware updated has failed.
Table 10: System Firmware Update Failure
NOTE: The communicator will report ´System Update Fail´ only if the panel becomes offline
after a remote firmware update session has started.
[095] SA Incoming Local Port
Default (0000)
[096] SA Outgoing Local Port
Default (0000)
[097] SA Call Up IP
Default (000.000.000.000)
[098] SA Call Up Port
Default (0000)
[099] SA Access Code
Default (FFFFFFFF)
Ethernet Receiver 1 Options
[101] Ethernet Receiver 1 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This account
code is used when transmitting heartbeat signals to the central station receiver. Signals received
from the panel will use the control panel account number. Valid range: 0000000001-
FFFFFFFFFE. Programming all 0 or all F will cause a module configuration trouble.
[102] Ethernet Receiver 1 DNIS
Default (000000)
The Dialed Number Information Service (DNIS) is used in addition to the account code to identify
the communicator module at the central station. Valid range: 000000 - 099999. Value is entered as
a leading 0 followed by the 5 digit DNIS. Format is Binary Coded Decimal (BCD).
Event
SIA
Identifier
SIA
Reporting
Code
Contact
ID
Qualifier
Contact
ID
Event
Code
Contact
ID
Reporting
Code
Contact
ID
User/Zone
[037] System FW Update Fail LU 0000 1 9 04 003