DHP-UM-020
Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600 Fax +45 7547 0611
vc@valcontrols.com www.valcontrols.com
Revision: 12
20/38
5.4.2 Advanced menu
Advanced menu Default Reset Description
1
Manual Control
Manual control of positioner.
1
Setpoint
Manual control of set point
2 Actuator Manual control of control valves
3 Actuator pulse Manual control of control valves using pulses only
4 Control valves Manual control of individual control valves
2 Signal Calibration Calibration of signals to control room
1 Control loop Calibration of 4-20 mA control signal
2 Transmitter loop Calibration of 4-20 mA transmitter signal
3 Position loop Calibration of 4-20 mA position loop
4 AI2 Calibration of 4-20 mA analogue input 1
5 AI3 Calibration of 4-20 mA analogue input 2
6 AI4 Calibration of 4-20 mA analogue input 3
7 AI5 Calibration of 4-20 mA analogue input 4
8 AO1 Calibration of 4-20 mA analogue output 1
9 AO2 Calibration of 4-20 mA analogue output 2
3 Configuration Configuration of in- and outputs
1 Valve function Configuration of valve control
1
Open
Not used A Menu to select valve position to open actuator
2 Close Not used A Menu to select valve position to close actuator
3 Stay-put Not used A Menu to select valve position to keep current actuator position
4 Fail position Off A Menu to select valve position at fail position
2 Position feedback Position feedback input
1 Position sensor A Potentiometer input
2 Position loop 4-20mA input
3 End position Configuration of endposition signal
1 Output signal 0% Not used A Select output which is active at 0%
2 Output signal 100% Not used A Select output which is active at 100%
3 Deadband 0.5% A Deadband for endpoint signal
4 Off/Local A Configure off/local signal
1 Off signal Not used A Select off signal input
2 Local signal Not used A Select local signal input
5 Man. valve control Configure the manaul control when in local mode
1 Open signal Not used A Select input to open valve
2 Close signal Not used A Select input to close valve
6 Emergency shutdown Configure Emergency shutdown
1 Input signal Not used A Select input to ESD signal
7 Error signal Configure error signal
1 Output signal Not used A Select output port for error signal
8 Ok signal Configure ok signal
1 Output signal Not used A Select output port for ok signal
9 Linear correction Calibrate the linearity of the position feedback
1 Status Enable the linear correction
2 Calibrate Perform the linear calibration

Other manuals for Val Controls I 24-B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Val Controls I 24-B Series and is the answer not in the manual?

Val Controls I 24-B Series Specifications

General IconGeneral
BrandVal Controls
ModelI 24-B Series
CategoryValve Positioners
LanguageEnglish

Related product manuals