7 Error no.
7.1 Mounting and settings
Solenoids are not configured
The Valve Function has not been configured in the menu
Configure the Valve Function in the advanced menu (3.1)
The positioner outputs goes to their fail position.
Potentiometer is not connected
The potentiometer has been selected as the position feedback signal, but there
is not connected a potentiometer to the positioner.
Connect a potentiometer to the positioner
Or
Change the position feedback signal to position loop in the advanced menu
(3.2)
The positioner outputs goes to their fail position.
Position loop is not connected
The position loop has been selected as the position feedback signal, but there
is not connected a signal to the positioner.
Connect a loop signal to the positioner
Or
Change the position feedback signal to potentiometer in the advanced menu
(3.2)
The positioner outputs goes to their fail position.
Control loop is not connected
A control loop has not been connected to the positioner
Connect a control loop to the positioner
The positioner outputs goes to their fail position.