70
9 Diagnostics and servicing
MINITRAC 31 • Foundation Fieldbus
41782-EN-211203
Error Cause Rectication
Output signal not stable Leveluctuations Set damping appropriate to the instrument via
the display and adjustment module or PACT-
ware/DTM
Output signal missing Electrical connection faulty Check connection according to chapter "
Connection steps" and if necessary, correct ac-
cording to chapter " Wiring plan"
Voltagesupplymissing Check cables for breaks; repair if necessary
Operatingvoltagetoolow Check, adapt if necessary
Thefollowingtabledescribespossiblefaultsthatmaynotgeneratean
error message:
Error Cause Rectication
The instrument signals cov-
eredwithoutbeingcoveredby
the measured medium
The instrument signals uncov-
eredwhilecoveredwiththe
measured medium
Voltagesupplymissing Check cables for breaks; repair if necessary
Operatingvoltagetoolow Check, adapt if necessary
Electrical connection faulty Check connection according to chapter "
Connection steps" and if necessary, correct ac-
cording to chapter " Wiring plan"
Electronics defective Changetheswitchingbehaviourofthesensors
under"Diagnosis/Simulation".Iftheinstrument
doesnotswitchover,senditinforrepair.
Buildupontheinnerwallof
the vessel
Remove buildup
Check the Delta I value.
Improvetheswitchingthreshold-carryouta
double point adjustment
Depending on the reason for the fault and the measures taken, the
steps described in chapter " Setup" must be carried out again or must
be checked for plausibility and completeness.
Should these measures not be successful, please call in urgent cases
theVEGAservicehotlineunderthephoneno.+49 1805 858550.
Thehotlineisalsoavailableoutsidenormalworkinghours,seven
daysaweekaroundtheclock.
Sinceweoerthisserviceworldwide,thesupportisprovidedin
English. The service itself is free of charge, the only costs involved are
the normal call charges.
9.4 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
InExapplications,onlyinstrumentsandelectronicsmoduleswithap-
propriate Ex approval may be used.
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The electron-
icsmodulesareadaptedtotherespectivesensoranddierinsignal
output or voltage supply.
Check output signal
(level detection)
Reaction after fault recti-
cation
24 hour service hotline

Table of Contents

Other manuals for Vega MINITRAC 31

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vega MINITRAC 31 and is the answer not in the manual?

Vega MINITRAC 31 Specifications

General IconGeneral
BrandVega
ModelMINITRAC 31
CategoryAccessories
LanguageEnglish

Related product manuals