Vertiv™ NetSure™ 5100 Series -48 VDC Power System User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
24
4.5 Adding an Inverter Module to an Existing Inverter Module Mounting
Assembly
To increase system current capacity, an inverter module can easily be added to an existing inverter module mounting assembly that
contains an empty inverter module mounting position.
Inverter modules can be inserted or removed with power applied (hot swappable).
NOTE!
Each inverter module locks into the module mounting shelf by means of a latch located on the bottom of the inverter
module. The latch and inverter module handle are interactive. Pushing the handle up into the inverter module’s front panel
causes the latch to extend to the locking position; pulling the handle down out from the inverter module’s front panel causes
the latch to retract. See
Figure 4.12
WARNING! To prevent damage to the latching mechanism, ensure the handle is in the open position when installing or
removing an inverter module. NEVER hold the handle in the closed position when installing an inverter module into a shelf.
Procedure
1. Unpack the inverter modules.
2. If present, remove blank cover panels from the module mounting positions into which inverter modules are to be installed.
3. Place the inverter module into an unoccupied mounting position without sliding it in completely.
4. Loosen the captive screw on the inverter module’s handle. Pull the handle down out from the inverter module’s front panel
(this will also retract the latch mechanism). See Figure 4.12.
5. Push the inverter module completely into the shelf.
6. Push the handle up into the inverter module’s front panel. This will lock the inverter module securely to the shelf. Tighten
the captive screw on the handle.
7. Repeat the above steps for each inverter module being installed in the system.
8. After the inverter modules are physically installed in the mounting shelf(s), they are ready for operation immediately after
power is supplied to them.

Table of Contents

Other manuals for Vertiv NetSure 5100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 5100 Series and is the answer not in the manual?

Vertiv NetSure 5100 Series Specifications

General IconGeneral
BrandVertiv
ModelNetSure 5100 Series
CategoryPower Supply
LanguageEnglish

Related product manuals