EasyManuals Logo
Home>Wilo>Control Unit>Easy Control MS-L 1x4kW

Wilo Easy Control MS-L 1x4kW User Manual

Wilo Easy Control MS-L 1x4kW
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
InstallationandoperatinginstructionsWilo-EasyControlMS-L1x4kW 31
INSTALLATION English
tobexedsecurelyandfunctionally.Theoperator
or the supplier is responsible for the provision of
the foundations and their suitability in terms of
dimensions, stability and strength.
The following ambient conditions must be ob-
served.
Ambient/operatingtemperature-30...+60°C
Max.relativehumidity:50%
Overow-proofassembly
Check the available planning documentation
(installation plans, design of installation location,
wiring diagram) is complete and correct.
Please also observe the applicable national acci-
dent prevention regulations and trade association
safety provisions.
5.3.1. Basic advice on xing the switchgear
The switchgear can be installed on various
structures (concrete wall, mounting rail etc.). For
thisreason,thexationmaterialsprovidedby
the customer must be suitable for the relevant
structure.
Observethefollowinginstructionsforthexation
material:
Ensure the proper edge clearance in order to
prevent the construction material from tearing or
chipping.
The size of the borehole depends on the size of
the bolts. The borehole should be 5 mm deeper
than the bolt length.
Drilling dust impairs holding strength. Therefore
Always blow or vacuum out the borehole.
Makesurethexationmaterialisnotdamaged
during assembly.
5.3.2. Assembling the switchgear
Wall-mounted installation
Fixtheswitchgeartothewallusing4screwsand
4 anchors.
1. Open the cover on the switchgear and place this
on the intended assembly area.
2. Draw the four holes on the assembly area.
Drillingdistances(WxH):140x219mm
Observe the information on the underside of
the switchgear too!
3. Drilltheholesaccordingtothespecicationsfor
thexationmaterialsused.
4. Fixtheswitchgearusingfourscrews(max.Ø:
4mm)andappropriateanchorsontothewall.
5.3.3. Positioning of signal transmitters
For automatic control of the connected pump,
a corresponding level control device must be
installed. This needs to be provided by the cus-
tomer.
Float switches may be used as signal transmitters.
Connection of level sensors or electrodes is not
possible! The corresponding signal transmit-
ters must be installed according to the system's
installation plan.
DANGER of explosions!
If the connected signal transmitters are
used in potentially explosive areas, there is a
danger of fatal injuries from explosions! The
connected signal transmitters must always be
used outside of potentially explosive areas.
Installation must always be carried out by a
qualied electrician.
Note the following:
Whenusingoatswitches,ensurethatthesecan
move freely in the collector tank (sump, reservoir).
The water level of the connected pump must not
fall below the minimum.
Themaximumswitchingfrequencyofthecon-
nectedpumpmustnotbeexceeded.
5.4. Electrical connection
POTENTIALLY fatal danger due to electrical
voltage
Incorrect electrical connections can cause fa-
tal electric shocks. Electrical connections may
only be made by a qualied electrician who is
approved by the local energy supplier, in ac-
cordance with locally applicable regulations.
DANGER of explosions!
If the connected pump and signal transmitter
are used in potentially explosive areas, there
is a danger of fatal injuries from explosions!
The connected pump and signal transmitter
must always be used outside of potentially
explosive areas. Installation must always be
carried out by a qualied electrician.
NOTE
Depending on the system's impedance and the
connectedconsumers'max.no.ofconnections/
hour,voltageuctuationsorvoltagedropsmay
occur. Always have the electrical connections
carried out by an electrician authorized by the
local energy supplier.
Observe the installation and operating in-
structions for the connected pump and signal
transmitters.
The mains connection current and voltage must
be as stated on the rating plate.
All-pole disconnecting, K-type circuit breakers
must be installed!
Max.fuseprotectiononmainsside:16A
On switchgears without a power supply separa-
tion device ("O" version: without main switch or
plug) this must be provided by the customer!
It is recommended a residual-current-operated
protection switch (RCD, type A, sinus wave-form
current) be installed. Observe the local laws and
regulations on this too!
Route the power supply cable in accordance with
the valid norms and regulations and according to
the wiring diagram.
Ground the system (switchgear and all electric
consumers) in accordance with the regulations.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Wilo Easy Control MS-L 1x4kW and is the answer not in the manual?

Wilo Easy Control MS-L 1x4kW Specifications

General IconGeneral
BrandWilo
ModelEasy Control MS-L 1x4kW
CategoryControl Unit
LanguageEnglish

Related product manuals