36 WILO SE 08/2013 Ed.04 DIN A4
English SHUTDOWN/DISPOSAL
7.4.2. If the direction of rotation is not correct
After activation, an audible signal sounds and all
LEDs ash in turn anti-clockwise:
The switchgear is incorrectly connected and the
connected pump is not operating correctly.
2 phases/conductors of the power supply on
mains side to the switchgear need to be swapped.
Pump running incorrectly:
Connection of the switchgear is correct. Con-
nection of the pump is incorrect. 2 phases of the
mains supply to the pump supply line need to be
swapped.
7.5. Activating automatic mode on the unit
Before automatic mode is switched on, check the
settings for the switching level and follow-up
time.
If all settings have been checked, you can switch
the unit on.
1. Press the "auto" button on the control panel.
2. The "auto" LED lights up and the unit now runs
inautomaticmode.Assoonastheoatswitch-
es provide a corresponding signal, the pump is
activated
"Pump ON" level: If the activation level is reached,
the pump switches on and the "Pump operation"
LED lights up permanently.
"Pump OFF" level: If the off level is reached, the
follow-up time set is active. During the follow-up
time,the"Pumpoperation"LEDashes.Oncethe
follow-uptimehasexpired,thepumpswitches
off and the "Pump operation" LED goes out.
NOTE
High-water protection is active in automatic
mode. When the activation level for high-water
protection is reached, the following occurs:
forced switch-on of the pump
a visual warning, the "High water" LED, lights up
permanently
an audible warning is emitted via a constant
signal.
the collective fault signal contact (SSM) is
activated.
7.6. Conduct during operation
When operating the switchgear, always follow the
locally applicable laws and regulations for work
safety, accident prevention and handling electri-
cal products.
To help to ensure safe working practice, the
responsibilities of employees should be clearly set
out by the operator. All personnel are responsible
for ensuring that regulations are observed.
Check the settings at regular intervals as to
whether they meet the current requirements. The
settings may need to be adjusted.
8. Shutdown/disposal
All work must be carried out with the greatest
care.
8.1. Deactivating automatic mode on the unit
1. Press the "Stop" button on the control panel.
2. The "Pump operation" LED goes out.
3. The"auto"LEDashes
4. The switchgear is in stand-by mode.
NOTE
High-water protection is not active in standby
mode. When the activation level for high-water
protection is reached, the following will not
occur:
forced switch-on of the pump
visual and audible warning
activation of the collective fault signal contact
(SSM).
8.2. Temporary shutdown
For temporary deactivation, the control is
switched off and switchgear is switched off via
the main switch.
The switchgear and the unit are now ready for
operationatanytime.Thedenedsettingsare
stored retentively in the switchgear and are not
discarded.
Make sure that the ambient conditions are ob-
served accordingly:
Ambient/operatingtemperature-30...+60°C
Airhumidity:40...50%
Prevent formation of condensate!
BEWARE of moisture!
Ingress of moisture will result in damage to
the switchgear. During standstill time, pay
attention to the permissible air humidity and
ensure the switchgear is stored so it is safe
from overowing.
1. Press the "Stop" button.
2. Wait until the "Pump operation" LED goes out.
3. The"auto"LEDashes.
4. Switch off the switchgear using the main switch
("OFF" position).
8.3. Final shutdown
POTENTIALLY fatal danger due to electrical
voltage
Incorrect procedures can cause fatal electric
shocks. This work may only be carried out by
a qualied electrician approved by the local
power supplier, in accordance with locally
applicable regulations.
1. Press the "Stop" button.
2. Wait until the "Pump operation" LED goes out.
3. The"auto"LEDashes.
4. Switch off the switchgear using the main switch
("OFF" position). On switchgears with a plug,
remove this from the socket.