Configuration
3–26 975-0170-01-01
Hi AC Freq
Full name High AC transfer frequency (AC over frequency level)
Configurable setting This setting lets you adjust the highest frequency at which the RS3000 no
longer qualifies AC as “good” and transfers to Invert.
You can adjust Hi AC Freq settings as follows:
When to use This setting lets you adjust the AC parameters when the AC supply is
outside the higher frequency range required for electrical equipment.
Outcome The highest frequency of the AC supply that will be qualified as “good”
by the inverter/charger can be varied.
Hi AC Freq [65Hz]
Range of values Increment Default
62 to 70 Hz 1 Hz 65 Hz