V5 series inverter
23
2-5-4. Connection of communication terminals
The communication port of this inverter is standard RS485 port.
With the following wiring methods, you can build up control system of one-host-one-slave or one-host-multi-slaves. Also,
the superior device (PC or PLC) can realize the functions such as real time monitor inverter, remote control, highly auto-
mated motion control.
Connection of inverter RS485 port and superior device:
Fig. 2-9 RS485-(RS485/232)-RS232 cable connection
Many inverters can be connected together through RS485, the PLC(or PC) is the host device, as shown in Fig.2-10;
Also, you can select one inveter as host and the other inverters are slaves, as shown in Fig.2-11.The more inverters are
connected, the communication system will be interfered seriously, the following wiring is recommended.
Fig. 2-10 Connection of PLC and inverters
(Inverters and motors are all grounded well)
Fig. 2-11 Connection of several inverters
Shield
cable
Inverter
RS485/RS232 converter
Terminal Name
5V power + +5V
Send data TXD
Receive data RXD
5V power - GND
Terminal Name
A Signal -
B Signal +
Terminal Name
Signal - A
Signal + B
Superior device
RS232(DB9)
Signal Pin
PE Cover
RXD 2
TXD 3
GND 5
DTR 4
DSR 6
RI 9
CD 1
RTS 7
CTS 8