V5 series inverter
75
4-2-7. Fault recording parameters (Group P6)
P6.00 last fault record Range: 0~23 0
P6.07 Last 2 fault record Range: 0~23 0
P6.08 Last 3 fault record Range: 0~23 0
P6.09 Last 4 fault record Range: 0~23 0
P6.10 Last 5 fault record Range: 0~23 0
P6.11 Last 6 fault record Range: 0~23 0
0: no fault
1~17: E-01~E-17 fault, refer to chapter 5.
P6.01 Output frequency of last fault Range: 0~upper limit of frequency 0
P6.02 Setting frequency of last fault Range: 0~upper limit of frequency 0
P6.03 Output current of last fault Range: 0~999.9A 0
P6.04 Output voltage of last fault Range: 0~999V 0
P6.05 DC bus voltage of last fault Range: 0~800V 0
P6.06 Module temperature of last fault Range: 0~100 0
4-2-8. Close-loop control parameters (Group P7)
Analog feedback control system:
Pressure value is input in VI, and feedback value (4~20mA) of pressure sensor is input to inverter CI then pass through
the internal PI adjustor to form analog close-loop control system, as shown in Fig4-32.
Fig.4-32 Analog feedback control system with internal PI
Principle diagram of inverter’s internal PI adjustor is shown below:
+ +
- +
Fig. 4-33 PI control principle diagram
The definition of close-loop value, feedback value, difference limit and proportion/integral parameter in Fig 4-33 are the
same to normal PI definition. Please refer to P7.01~P7.11. The relationship between preset value and expect feedback val-
ue is shown in Fig 4-34. The preset value is based on 10V; the feedback value is based on 20mA.
The aim of preset value adjustment and feedback value adjustment is to confirm the their relationship and size, as shown in
Close-loop
preset value
Preset value
adjustment
(P7.06,P7.08)
Difference
limit (P7.13)
Close-loop
adjust feature
(P7.14)
Proportion