V5 series inverter
36
P0.15 Linear time of S
curve
10.0%~80.0%(Acc/Dec time)
P0.14+P0.15<90%
0.1% 60.0% ○
P0.16 Acc/Dec time unit 0: second
1: minute
0 0 ×
P0.17 Accerlate time 1 0.1~6000.0 0.1 10.0 ○
P0.18 Decerlate time 1 0.1~6000.0 0.1 10.0 ○
P0.19 High limit frequency Lowest frequency ~highest output
frequency P0.06
0.01Hz 50.00Hz ×
P0.20 Low limit frequency 0.00Hz~highest frequency 0.01Hz 0.00Hz ×
P0.21 Running mode of
lowest frequency
0: running at lowest frequency
1: stop
1 0 ×
P0.22 V/F curve setting 0: constant torque curve
1: torque-reducing curve 1 (1.2
powers)
2: torque-reducing curve 2 (1.7
powers)
3: torque-reducing curve 3 (2.0
powers)
4: multi-segment V/F curves
1 0 ×
P0.23 V/F frequency value
P1
0.00~P0.25 0.01Hz 0.00Hz ×
P0.24 V/F voltage value
V1
0~ P0.26 0.1% 0.0% ×
P0.25 V/F frequency value
P2
P0.23 ~ P0.27 0.01Hz 0.00Hz ×
P0.26 V/F voltage value
V2
P0.24 ~ P0.28 0.1% 0.0% ×
P0.27 V/F frequency value
P3
P0.25 ~ P0.07 basic running
frequency
0.01Hz 0.00Hz ×
P0.28 V/F voltage value
V3
P0.26 ~ 100.0% 0.1% 0.0% ×
2. Frequency parameter (Group P1)
Group P1: reference frequency parameter
Parameter Name Setting range
Minmum
unit
Default setting
Change
P1.00 Time constant of
analog filter
0.01~30.00s 0.01s 0.20s ○
P1.01 The gain of VI
channel
0.01~9.99 0.01 1.00 ○
P1.02 min setting value of
VI
0.00~P1.04 0.01V 0.00V ○
P1.03 Frequency of the
min setting of VI
0.00~highest frequency 0.01Hz 0.00Hz ○
P1.04 Max setting of VI P1.04~10.00V 0.01V 10.00V ○
P1.05 Frequency of the
max setting of VI
0.00~highest frequency 0.01Hz 50.00Hz ○
P1.06 The gain of CI
channel
0.01~ 9.99 0.01 1.00 ○
P1.07 Min setting of CI 0.00~ P1.09 0.01V 0.00V ○
P1.08 Frequency of the
min setting of CI
0.00~highest frequency 0.01Hz 0.00Hz ○