246699-YTG-D-1208
12 Johnson Controls Unitary Products
TABLE 3: DF CAPACITY RATINGS
Size
(Tons)
Model
Cooling Capacity
ARI Ratings
*
CFM
Sound
Rating
(dB)
Nominal
Electric
Heat
Capacity
(kW)
Gas Heat Capacity
Gas
Line
Size
(in. OD)
MBH EER IPLV
Input
(MBH)
Output
(MBH)
Seasonal
Efficiency
(%)
Temp.
Rise
(°F)
078
(6-1/2)
Cooling
Only
75 10.4 11.0 2600 84
--- - --
Electric
Heat
9, 18, 24,
36
-- - - -
Gas Heat - 120 96 80 20-50 3/4
Gas Heat - 180 144 80 35-65 3/4
090
(7-1/2)
Cooling
Only
87 10.5 11.6 2516 84
--- - --
Electric
Heat
18, 36 - - - - -
Gas Heat - 120 96 80 15-45 3/4
Gas Heat - 180 144 80 30-60 3/4
102
(8-1/2)
Cooling
Only
99 10.4 10.39 3055 84
--- - --
Electric
Heat
9, 18, 24,
36
-- - - -
Gas Heat - 120 96 80 15-45 3/4
Gas Heat - 180 144 80 30-60 3/4
120
(10)
Cooling
Only
115 10.4 10.0 4000 90
--- - --
Electric
Heat
18, 24, 36,
54
-- - - -
Gas Heat - 180 144 80 20-50 3/4
Gas Heat - 240 192 80 35-65 3/4
* Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
Rated in accordance with ARI 270 standard.
See Table 17.
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING MIN. MAX.
208/230-3-60
187 252
460-3-60
432 504
575-3-60
540 630

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York Predator DF 090 and is the answer not in the manual?

York Predator DF 090 Specifications

General IconGeneral
BrandYork
ModelPredator DF 090
CategoryAir Conditioner
LanguageEnglish

Related product manuals