246699-YTG-D-1208
12 Johnson Controls Unitary Products
TABLE 3: DF CAPACITY RATINGS
Size
(Tons)
Model
Cooling Capacity
ARI Ratings
*
CFM
Sound
Rating
(dB)
†
Nominal
Electric
Heat
Capacity
‡
(kW)
Gas Heat Capacity
Gas
Line
Size
(in. OD)
MBH EER IPLV
Input
(MBH)
Output
(MBH)
Seasonal
Efficiency
(%)
Temp.
Rise
(°F)
078
(6-1/2)
Cooling
Only
75 10.4 11.0 2600 84
--- - --
Electric
Heat
9, 18, 24,
36
-- - - -
Gas Heat - 120 96 80 20-50 3/4
Gas Heat - 180 144 80 35-65 3/4
090
(7-1/2)
Cooling
Only
87 10.5 11.6 2516 84
--- - --
Electric
Heat
18, 36 - - - - -
Gas Heat - 120 96 80 15-45 3/4
Gas Heat - 180 144 80 30-60 3/4
102
(8-1/2)
Cooling
Only
99 10.4 10.39 3055 84
--- - --
Electric
Heat
9, 18, 24,
36
-- - - -
Gas Heat - 120 96 80 15-45 3/4
Gas Heat - 180 144 80 30-60 3/4
120
(10)
Cooling
Only
115 10.4 10.0 4000 90
--- - --
Electric
Heat
18, 24, 36,
54
-- - - -
Gas Heat - 180 144 80 20-50 3/4
Gas Heat - 240 192 80 35-65 3/4
* Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
† Rated in accordance with ARI 270 standard.
‡ See Table 17.
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING MIN. MAX.
208/230-3-60
187 252
460-3-60
432 504
575-3-60
540 630