64 Johnson Controls Unitary Products
FIGURE 40 - UNIT CONTROL BOARD
TABLE 41: UNIT CONTROL BOARD FLASH CODES
FLASH CODE DESCRIPTION
GREEN
LED
16
RED
LED
8
RED
LED
4
RED
LED
2
RED
LED
1
On Steady This is a Control Failure - - - - -
1 Flash Not Applicable - - - - -
2 Flashes
Control waiting ASCD
*
Flashing Off Off On Off
3 Flashes HPS1 Compressor Lockout Off Off Off On On
4 Flashes HPS2 Compressor Lockout Off Off On Off Off
5 Flashes LPS1 Compressor Lockout Off Off On Off On
6 Flashes LPS2 Compressor Lockout Off Off On On Off
7 Flashes FS1 Compressor Lockout Off Off On On On
8 Flashes FS2 Compressor Lockout Off On Off Off Off
9 Flashes Ignition Control Locked Out / Ignition Control Failure Off On Off Off On
10 Flashes
Compressors Locked Out on Low Outdoor Air Temperature
1
Flashing On Off On Off
11 Flashes
Compressors locked out because the Economizer is using free
Cooling
1
Flashing On Off On On
12 Flashes Unit Locked Out due to Fan Overload Switch Failure Off On On Off Off
13 Flashes
Compressor Held Off due to Low Voltage
1
Flashing On On Off On
14 Flashes EEPROM Storage Failure Off On On On Off
OFF No Power or Control Failure Off Off Off Off Off
*.
Non-alarm condition.
Check
Alarm
History
Reset All
ASCDs for
One Cycle
Non Alarm
Condition Green
LED Flashing
Current Alarm
Flashed
Red LED

Table of Contents

Other manuals for York PREDATOR MagnaDRY DR090

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York PREDATOR MagnaDRY DR090 and is the answer not in the manual?

York PREDATOR MagnaDRY DR090 Specifications

General IconGeneral
BrandYork
ModelPREDATOR MagnaDRY DR090
CategoryAir Conditioner
LanguageEnglish

Related product manuals