LIMITATIONS
These units must be installed in accordance with the follow-
ing:
In U.S.A.
:
1. National Electrical Code, ANSI/NFPA No. 70 - Latest
Edition
2. National Fuel Gas Code, ANSI Z223.1 - Latest Edition
3. Gas-Fired Central Furnace Standard, ANSI Z21.47a. -
Latest Edition
4. Local building codes, and
5. Local gas utility requirements
In Canada
:
1. Canadian Electrical Code, CSA C22.1
2. Installation Codes, CSA - B149.1.
3. Local plumbing and waste water codes, and
4. Other applicable local codes.
Refer to Tables 1 & 2 for unit application data.
After installation, gas fired units must be adjusted to obtain a
temperature rise within the range specified on the unit rating
plate.
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer’s and/or customer’s
expense.
Size of unit for proposed installation should be based on heat
loss/heat gain calculation made according to the methods of
Air Conditioning Contractors of America (ACCA).
This furnace is not to be used for temporary heating of build-
ings or structures under construction.
This product must be installed in strict compliance with
the enclosed installation instructions and any applica-
ble local, state and national codes including, but not
limited to, building, electrical, and mechanical codes.
The furnace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing at pressures in excess of 1/2
PSIG.
Pressures greater than 1/2 PSIG will cause gas valve
damage resulting in a hazardous condition. If it is sub-
jected to a pressure greater than 1/2 PSIG, the gas
valve must be replaced.
The furnace must be isolated from the gas supply pip-
ing system by closing its individual manual shut-off
valve during any pressure testing of the gas supply pip-
ing system at test pressures equal to or less than 1/2
PSIG.
The Simplicity® control board used in this product
will effectively operate the cooling system down to
0°F when this product is applied in a comfort cooling
application for people. An economizer is typically
included in this type of application. When applying
this product for process cooling applications (com-
puter rooms, switchgear, etc.), please reference
applications bulletin AE-011-07 or call the applica-
tions department for Unitary Products @ 1-877-
UPG-SERV for guidance. Additional accessories
may be needed for stable operation at temperatures
below 30° F.

Table of Contents

Other manuals for York PREDATOR MagnaDRY DR090

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York PREDATOR MagnaDRY DR090 and is the answer not in the manual?

York PREDATOR MagnaDRY DR090 Specifications

General IconGeneral
BrandYork
ModelPREDATOR MagnaDRY DR090
CategoryAir Conditioner
LanguageEnglish

Related product manuals