SECTION 4 - PRINTING
JOHNSON CONTROLS
217
FORM 160.54-O1
ISSUE DATE: 9/10/2014
4
FIGURE 74 - SAMPLE PRINTOUT (ADAPTIVE
CAPACITY CONTROL EXISTING MAP POINTS
REPORT)
FIGURE 73 - SAMPLE PRINTOUT (ADAPTIVE
CAPACITY CONTROL NEW MAP POINT REPORT)
Log Time: Mon 12:45:39 PM 21 Jun 1999
D-P/P= 0.92; Prv Pos= 56; Freq= 39 Hz
Surge Type = Delta P/P Surge
Leaving Chilled Active Setpoint = 45.0 ~F
Leaving Chilled Liquid Temperature = 50.0 ~F
Return Chilled Liquid Temperature = 59.3 ~F
Leaving Condenser Liquid Temperature = 85.0 ~F
Return Condenser Liquid Temperature = 94.9 ~F
Evaporator Pressure = 7.2 Psig
Condenser Pressure = 13.8 Psig
% Full Load Amps = 94 %
D-P/P = 1.20; Prv Pos = 89; Freq = 58 Hz
D-P/P = 1.41; Prv Pos = 71; Freq = 46 Hz
D-P/P = 0.98; Prv Pos = 73; Freq = 52 Hz
D-P/P = 0.71; Prv Pos = 86; Freq = 39 Hz
D-P/P = 0.86; Prv Pos = 53; Freq = 48 Hz
D-P/P = 1.14; Prv Pos = 76; Freq = 51 Hz
D-P/P = 0.84; Prv Pos = 84; Freq = 37 Hz
D-P/P = 0.99; Prv Pos = 63; Freq = 46 Hz

Table of Contents

Other manuals for York YK Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YK Series and is the answer not in the manual?

York YK Series Specifications

General IconGeneral
BrandYork
ModelYK Series
CategoryChiller
LanguageEnglish

Related product manuals