FORM 160.54-O1
ISSUE DATE: 9/10/2014
JOHNSON CONTROLS
40
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
be at minimum; the 100% output will be at maximum.
If set to reverse, the 0.0% output will be at maximum;
the 100% output will be at minimum.
Control Valve Control Mode
Displays whether the Control Valve is in automatic or
manual control.
PROGRAMMABLE
Head Pressure Setpoint
(15.0 to 60 PSID; default 23.0 PSID) Sets the pressure
differential to which the Control Valve will control the
Head Pressure.
Control Valve Output Settings – Type
(0-10v or 4 to 20mA; default 0-10v) Sets the output
signal to the Control Valve to be in the form of either 0
to 10VDC or 4 to 20mA.
Control Valve Output Settings – PID Output
(Direct or Reverse) Allows the output signal to the
Control Valve to be set to direct or reverse acting.
When set to direct, the voltage or current signal to the
Control Valve is at minimum for a 0% command and at
maximum for a 100% command. When set to reverse,
the voltage or current signal to the Control Valve is at
maximum for a 0% command and at minimum for a
100% command.
Control Valve Output Settings – Set
(0.0% to 100%; default 0.0%) Allows the Control
Valve to be manually set to a pre-determined position
between 0.0% and 100%.
Control Valve Output Settings – Auto
Places the Control Valve in automatic control.
Change Setpoints
Use to enter the Head Pressure Control PID variables
below. Pressing this key places a green box around the
first changeable setpoint. Use the up/down, left/right
arrows to place the selection box around the desired
setpoint. With the setpoint selected, press the ENTER
() key. A dialog box appears with the range of set-
tings. Using the NUMERIC keys, enter desired value.
Then, press the ENTER () key.
Head Pressure Control – P
Sets the Proportional Gain of the Head Pressure Con-
trol (0.00 to 5.00; default 2.00). Use the CHANGE
SETPOINTS key as described above to select/enter
this setpoint.
Head Pressure Control – I
Sets the Integral Gain of the Head Pressure Con-
trol (0.00 to 5.00; default 2.00). Use the CHANGE
SETPOINTS key as described above to select/enter
this setpoint.
Head Pressure Control – D
Sets the Derivative Gain of the Head Pressure Con-
trol (0.00 to 5.00; default 0.00). Use the CHANGE
SETPOINTS key as described above to select/enter
this setpoint.
NAVIGATION
Home
Returns user to HOME Screen.
Condenser
Returns user to CONDENSER Screen.

Table of Contents

Other manuals for York YK Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YK Series and is the answer not in the manual?

York YK Series Specifications

General IconGeneral
RefrigerantR-134a
EfficiencyHigh
ApplicationCommercial and Industrial
TypeWater-cooled
Frequency50/60 Hz

Related product manuals