Memory
Data Value Unit
User Program memory 1 MByte
User Data memory (thereof 120 kBytes saved) 1 MByte
Minimum Performance
Data Value Unit
Cycle time Binary 0.05 µs/Instruction
Cycle time Word 0.06 µs/Instruction
Cycle time floating-point 0.50 µs/Instruction
Voltages, according to EN 61131-2
Data Value Unit
Process and supply voltage (without ripple) 24 ( – 15 %, +20 %) V DC
Absolute limits (including ripple) 19.2 ... 30 V
Ripple < 5 %
Protection against reverse polarity 10 s
DANGER!
Exceeding the maximum process or supply voltage range (< –35 V DC or > +35 V DC) could lead to
unrecoverable damage of the system.