1.2 Document history
Rev. Description of version / changes Who Date
1.0.0 First release ABB 19.12.2012
1.0.1 Minor typos were corrected. TÜV certificate was added.
The text was changed in the document:
n Safety I/O inputs and outputs are not electrically isolated from
the other electronic circuitry of the module.
n The safety values for safety outputs of DX581-S (-XC) module
are only valid if the parameter “Detection” is set to "On".
n DC (Diagnostic Coverage) for DX581-S (-XC) module shall be
≥ 94 %.
n The clarification was added that the boot project update on
SM560-S is possible only if no boot project is loaded on SM560-
S.
n Not more than one communication error (CE_CRC or
Host_CE_CRC output signals become equal to TRUE) per 100
hours is allowed to be acknowledged by the operator using
OA_C input signal without consulting the responsible safety per-
sonnel.
n SM560-S cycle time shall be included three times instead of two
times in Safety Function Response Time calculation.
n The values for input delay accuracy in Safety Function
Response Time calculation were updated.
n Update of Appendix A with system data for AC500-S-XC.
ABB 08.03.2013
1.0.2 Words "Original Instructions" have been added to document title ABB 17.04.2015
Introduction
Document history
30.03.2017AC500-S8