NOTICE!
Risk of damage to I/O modules!
Do not perform hot swapping if any I/O module with firmware version lower than
3.0.14 is part of the I/O configuration.
For min. required device index see table below.
Hot swapping is only allowed for I/O modules.
Processor modules and communication interface modules must not be removed
or inserted during operation.
Device Min. required device index for I/O module as of
FW Version 3.0.14
AI523 (-XC) D2
AI531 D4
AI531-XC D2
AI561 B2
AI562 B2
AI563 B3
AO523 (-XC) D2
AO561 B2
AX521 (-XC) D2
AX522 (-XC) D2
AX561 B2
CD522 (-XC) D1
DA501 (-XC) D2
DC522 (-XC) D2
DC523 (-XC) D2
DC532 (-XC) D2
DC561 B2
DC562 A2
DI524 (-XC) D2
DI561 B2
DI562 B2
DI571 B2
DI572 A1
DO524 (-XC) A3
DO526 A2
DO526-XC A0
DO561 B2
DO562 A2
DO571 B3
CI542-DP
2019/11/15 3ADR024117M02xx, 11, en_US 81

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB AC500 Series and is the answer not in the manual?

ABB AC500 Series Specifications

General IconGeneral
Modular DesignYes
Protection ClassIP20
SeriesAC500
Mounting TypeDIN rail
Programming SoftwareAutomation Builder
Communication InterfacesEthernet, Serial
Digital InputsAvailable
Digital OutputsAvailable
Analog InputsAvailable
Analog OutputsAvailable
Digital Input Voltage24V DC
Digital Output Voltage24V DC
Analog Input TypeVoltage, Current, RTD, Thermocouple
Analog Output TypeVoltage, Current
ProtectionShort-circuit
CPUVarious models available
Digital I/OExpandable
Analog I/OExpandable
Power Supply24V DC
CertificationsCE, UL, cUL, ATEX
MemoryDepends on CPU model

Related product manuals