1-198 ACH550-UH User’s Manual
Embedded fieldbus
Feedback from the drive – EFB
Pre-defined feedback
Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data. For a complete listing, see input word/point/object
listings in the technical data for the appropriate protocol starting on page 1-205.
Note: With Modbus, any parameter can be accessed using the format: 4 followed by
the parameter number.
Mailbox read/write
The ACH550 provides a “Mailbox” function to access parameters that have not been
pre-defined by the protocol. Using mailbox, any drive parameter can be identified
Drive Parameter
Protocol Reference
Modbus N2 FLN BACnet
0102 SPEED 40102 AI3 5 AV0
0103 FREQ OUTPUT 40103 AI1 2 AV1
0104 CURRENT 40104 AI4 6 AV4
0105 TORQUE 40105 AI5 7 AV5
0106 POWER 40106 AI6 8 AV6
0107 DC BUS VOLT 40107 AI11 13 AV2
0109 OUTPUT VOLTAGE 40109 AI12 14 AV3
0115 KWH COUNTER 40115 AI8 10 AV8
0118 DI1-3 STATUS – bit 1 (DI3) 40118 BI10, BI11,
BI12,
70, 71, 72 BI6, BI7, BI8
0122 RO1-3 STATUS 40122 BI4, BI5, BI6 76, 77, 78 BI0, BI1, BI2
0301 FB STATUS WORD – bit 0 (STOP) 40301 bit 0 BI1 23 BV0
0301 FB STATUS WORD – bit 2 (REV) 40301 bit 2 BI2 21 BV1