1-320 ACH550-UH User’s Manual
Technical data
Air flow, 500…600 volt drives
The following table lists heat loss and air flow data for 500…600 volt drives.
Dimensions and weights
The dimensions and mass for the ACH550 depend on the frame size and enclosure
type. If unsure of frame size, first, find the “Type” code on the drive labels. Then look
up that type code in the Technical data on page 1-297, to determine the frame size.
A complete set of dimensional drawings for ACH550 drives is located in the ACH550
Technical Reference manual.
-368A-4 R8 6850 23000 700 1220
-414A-4 R8 7000
24000 700 1220
-486A-4 R8 7600
26000 700 1220
-526A-4 R8 7800
27000 700 1220
-602A-4 R8 8100 28000 700 1220
-645A-4 R8 9100
31000 700 1220
Type Code
Frame Size
Heat Loss Air Flow
ACH550-UH-
see below
W BTU/Hr m
3
/h ft
3
/min
Three-phase supply voltage, 500…600 V
-02A7-6 R2 46
157 88 52
-03A9-6 R2 68 232 88 52
-06A1-6 R2 124 423 88 52
-09A0-6 R2 170
581 88 52
-011A-6 R2 232 792 88 52
-017A-6 R2 337 1150 88 52
-022A-6 R3 457
1560 134 79
-027A-6 R3 562 1918 134 79
-032A-6 R4 667 2256 280 165
-041A-6 R4 907
3096 280 165
-052A-6 R4 1120 3820 280 165
-062A-6 R4 1295 4420 280 165
-077A-6 R6 1504
5136 405 238
-099A-6 R6 1821
6219 405 238
-125A-6 R6 2442 8339 405 238
-144A-6 R6 2813
9607 405 238
Drive Heat Loss Air Flow
ACH550-xx- Frame Size W
BTU/Hr m
3
/h ft
3
/min