ABB Chapter 8 - Changing Diodes and IGCTs in 7/9 MVA Phase Modules
ACS 6000 Maintenance Manual 3BHS202077 ZAB E01 Rev. C 8-13 (18)
4 Continue with section
8.4.4 Finishing Steps
for remounting the
capacitors, adjusting the clamp pressure and installing the phase
module.
8.4.4 Finishing Steps
1 Insert the isolator disk and center it.
2 Remount the capacitors.
Proper alignment is important to prevent distortion and lateral forces
acting on the capacitors.
When tightening the nuts pay attention not to exceed the maximum
tightening torque (M8 nuts: 8 Nm).
Exceeding the maximum value may result in damage of the
capacitors.
3 Adjust the clamp pressure of the stack.
Insert the pressure adjusting bolt and tighten it until the clamp
pressure loading gauge is released.
4 Refit the clamp pressure loading gauge in its storage place.
5 Check the blocking/unblocking behaviour of the new diode. Refer to
Chapter 2 - Checking IGCTs and Diodes
.
6 Remount the phase module in the cabinet following section
7.3
Installing a Phase Module
.

Table of Contents

Other manuals for ABB ACS 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS 6000 and is the answer not in the manual?

ABB ACS 6000 Specifications

General IconGeneral
BrandABB
ModelACS 6000
CategoryController
LanguageEnglish

Related product manuals