Technical data
96
Frame sizes R5 and R6
Choose between gG and aR fuses according to the table under Quick guide for
selecting between gG and aR fuses on page 100, or verify the operating time by
checking that the short-circuit current of the installation is at least the value
given in the fuse table. The short-circuit current can be calculated as follows:
where
I
k2-ph
= short-circuit current in symmetrical two-phase short-circuit (A)
U = network line-to-line voltage (V)
R
c
= cable resistance (ohm)
Z
k
= = z
k
· U
N
2
/S
N
= transformer impedance (ohm)
z
k
= transformer impedance (%)
U
N
= transformer rated voltage (V)
S
N
= nominal apparent power of the transformer (kVA)
X
c
= cable reactance (ohm).
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0004-5 4.7 10 483 500 ABB Control OFAF000H10 000
-0005-5 5.9 10 483 500 ABB Control OFAF000H10 000
-0006-5 7.7 10 483 500 ABB Control OFAF000H10 000
-0009-5 10.0 16 993 500 ABB Control OFAF000H16 000
-0011-5 12.5 16 993 500 ABB Control OFAF000H16 000
-0016-5 17 20 1620 500 ABB Control OFAF000H20 000
-0020-5 23 25 3100 500 ABB Control OFAF000H25 000
-0025-5 31 40 9140 500 ABB Control OFAF000H40 000
-0028-5 36 50 15400 500 ABB Control OFAF000H50 000
-0030-5 41 50 15400 500 ABB Control OFAF000H50 000
-0040-5 47 63 21300 500 ABB Control OFAF000H63 000
-0045-5 54 63 21300 500 ABB Control OFAF000H63 000
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0011-7 12 16 1100 690 ABB Control OFAA000GG16 000
-0016-7 15 20 2430 690 ABB Control OFAA000GG20 000
-0020-7 21 25 4000 690 ABB Control OFAA000GG25 000
-0025-7 24 32 7000 690 ABB Control OFAA000GG32 000
-0030-7 33 35 11400 690 ABB Control OFAA000GG35 000
-0040-7 35 50 22800 690 ABB Control OFAA000GG50 000
PDM code:00096931-J
ACS800-04
size
Input
current
Fuse
AA
2
s V Manufacturer Type IEC size
I
k2-ph
=
2 ·
R
c
2
+ (Z
k
+ X
c
)
2
U