Technical data
100
Quick guide for selecting between gG and aR fuses
The table below is a short cut in selecting between gG and aR fuses. The
combinations (cable size, cable length, transformer size and fuse type) in the table
fulfil the minimum requirements for the proper operation of the fuse.
Note 1: The supply transformer minimum power in kVA is calculated with a z
k
value of 6% and
frequency 50 Hz.
Note 2: The table is not intended for transformer selection - that must be done separately.
ACS800-01 size Cable type Supply transformer minimum apparent power S
N
(kVA)
Copper Aluminium Maximum cable length with gG fuses Maximum cable length with aR fuses
10 m 50 m 100 m 10 m 100 m 200 m
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0025-2 3×25 Cu 3×35 Al 33 39 28 28
-0030-2 3×35 Cu 3×50 Al 46 56 34 34
-0040-2 3×50 Cu 3×70 Al 60 73 42 42
-0050-2 3×70 Cu 3×95 Al 75 89 58 71
-0060-2 3×95 Cu 3×120 Al 89 110 68 71
-0070-2 3×120 Cu 3×185 Al 110 120 84 84
Three-phase supply voltage 380 V, 400 V or 415 V
-0040-3 3×25 Cu 3×35 Al 56 59 72 50 50 50
-0050-3 3×35 Cu 3×50 Al 79 85 110 60 60 60
-0060-3 3×50 Cu 3×70 Al 110 120 140 72 72 72
-0075-3 3×70 Cu 3×95 Al 130 140 160 99 99 140
-0070-3 3×70 Cu 3×95 Al 130 140 170 100 100 140
-0100-3 3×95 Cu 3×120 Al 160 170 200 120 120 140
-0120-3 3×120 Cu 3×185 Al 180 190 220 150 150 150
-0135-3 3×150 Cu 3×240 Al 210 220 260 160 160 160
-0165-3 3×185 Cu 3×240 Al 250 270 320 190 190 200
-0205-3 3×240 Cu 2×(3×95) Al 232 257 310 134 153 196
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0050-5 3×25 Cu 3×35 Al 67 70 79 56 56 56
-0060-5 3×25 Cu 3×50 Al 95 110 130 68 68 68
-0070-5 3×35 Cu 3×70 Al 130 140 160 83 83 83
-0105-5 3×70 Cu 3×95 Al 160 170 190 130 130 150
-0100-5 3×70 Cu 3×95 Al 160 170 190 110 120 150
-0120-5 3×95 Cu 3×120 Al 190 200 220 140 140 150
-0140-5 3×95 Cu 3×150 Al 190 200 220 160 160 160
-0165-5 3×150 Cu 3×240 Al 250 260 290 200 200 200
-0205-5 3×185 Cu 3×240 Al 290 320 360 230 230 230
-0255-5 3×240 Cu 2×(3×95) Al 289 312 355 167 185 218
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0050-7 3×16 Cu 3×25 Al 65 67 70 63 63 63
-0060-7 3×16 Cu 3×25 Al 70 70 70 70 70 70
-0070-7 3×25 Cu 3×50 Al 95 95 99 95 95 95
-0100-7 3×35 Cu 3×50 Al 130 140 150 110 110 110
-0120-7 3×50 Cu 3×70 Al 180 180 190 140 140 140
-0145-7 3×70 Cu 3×95 Al 220 220 240 160 160 160
-0175-7 3×95 Cu 3×120 Al 260 260 280 200 200 200
-0205-7 3×95 Cu 3×150 Al 340 360 390 230 230 230
PDM code: 00556489 A
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS800-U4 and is the answer not in the manual?

ABB ACS800-U4 Specifications

General IconGeneral
BrandABB
ModelACS800-U4
CategoryController
LanguageEnglish

Related product manuals