52 Technical data
Free space requirements
For cabinet dimensions, refer to Dimension drawings on page 45.
Adequate free space above the inverter has to be reserved for installation and cooling.
Required free space in from of the inverter for door opening, power module and LCL filter
replacement is 850 mm.
Cooling data
Required cooling air flow
• Main circulation: 8000 m
3
/h (4720 ft
3
/min)
• 1 ISU cabinet 3900 m
3
/h
• AC cabinet: 1300 m
3
/h
• DC cabinet: 615 m
3
/h
• Optional DC cabinet: 245 m
3
/h
• AUX cabinet: 260 m
3
/h
• Total: 10000 m
3
/h (5880 ft
3
/min)
Terminal and lead-through data for the AC power
connections
• Cable lead-throughs 30 pcs
• Cable outer diameter 8...60 mm/lead-through
• Tightening torques: *M12 70 Nm
Terminal and lead-through data for the DC power
connections
16 DC inputs • Cable lead-throughs 32 pcs
• Cable outer diameter 5...60 mm/lead-through
• Tightening torques: *M12 70 Nm
24 DC inputs • Cable lead-throughs 48 pcs
• Cable outer diameter 5...60 mm/lead-through
• Tightening torques: *M12 70 Nm