Maintenance
42/68-165-EN RHD250 ... 4000 29
Pos: 14.1 /Überschri ften/1/V - Z/War tung @ 10\mod_1181642125390_310 1.doc @ 103817
6 Maintenance
Pos: 14.2 /Wartung / Repara tur/Aktorik/ Antriebe/Allgemein/ Wartung @ 10\mod_11816402 90218_3101.doc @ 103695
Important
All maintenance activities may only be performed by properly qualified persons.
Contrac actuators feature a robust construction. As a result, they are highly reliable and require
minimal maintenance. The maintenance intervals depend upon the effective load and are
therefore not specified here.
The built-in microprocessor evaluates the actual load factors (e.g. torques, forces,
temperatures, etc.) and derives the remaining operating time until the next routine maintenance
is required.
Use the configuration program to view this information.
Pos: 14.3 /Überschri ften/1.1/1-spa ltig/G - I/Inspektion und Überholung @ 10\mod_11816 42170921_3101.doc @ 103840
6.1 Inspection and overhaul
Pos: 14.4 /Wartung / Repara tur/Aktorik/ Antriebe/Elektr. Sc hwenkantriebe/Allge mein/Inspektion und Überholung RHD @ 16\mod_1197 275309500_3101.doc @ 145205
Only use genuine spare parts such as ball bearings, gaskets and oil may be used to
overhaul the actuators.
Proceed acc. to table when performing maintenance activities.
Inspection or maintenance is due after the time specified in the table.
Overhaul intervals:
Interval Measures
1 x per year Visual check of the gaskets for leaks, change
if necessary.
Change oil, roller bearings and gaskets on
motor and gearing.
max. every 10 years, preferably after the
expiry of the calculated remaining service life
Check gear wheels for wear; replace if
necessary.
Don’t drive the actuator during the oil check.
Make sure that no chippings or other material get into the gearbox during the maintenance
work.
Pos: 14.5 /====== = Seitenumbruch ======= = @ 0\mod_1126532365768_3101.doc @ 3830

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RHD250 and is the answer not in the manual?

ABB RHD250 Specifications

General IconGeneral
BrandABB
ModelRHD250
CategoryController
LanguageEnglish

Related product manuals