Troubleshooting
10 TROUBLESHOOTING
The table below lists the anomalies of operation of the unit, the relevant causes and the corrective measures.
For anomalies of any other type or not listed, contact one of Itelco-Clima’s Service Centre for technical assis-
tance.
Anomaly Cause Operation
The unit continues to work,
but without cooling.
Insufficient charge of refrigerant. Refill.
The dehydrating filter is clogged. Replace.
Ice on the suction line. Wrong calibration of overheating.
Increase overheating.
Check the charge.
Excessive noise.
Vibration of lines.
Check the clamping brackets,
if any.
Whistler emitted by the thermostatic
expansion valve.
Refill.
Check the dehydrating filter.
Noisy compressor. Seized bearings; replace the com-
pressor.
Check that the compressor’s locknuts
are tightened.
Low oil level in the
compressor.
One or more gas or oil leaks in the
circuit
Identify and remove leaks.
Mechanical failure of the compres-
sor.
Request the intervention of a Service
Centre.
Anomaly of the oil heater of the
compressor’s base.
Check the electric circuit and the resis-
tor of the heater of the motor base,
and replace defective components.
Manuale CLS-CLH2 7.2.2005 10:23 Pagina 78

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Airwell Itelco-Clima CLS 182 STD and is the answer not in the manual?

Airwell Itelco-Clima CLS 182 STD Specifications

General IconGeneral
BrandAirwell
ModelItelco-Clima CLS 182 STD
CategoryChiller
LanguageEnglish

Related product manuals