Develop Applications Chapter 10
Interrupt the Execution of Logic and Execute the Fault Handler
Depending on your application, you can want an I/O connection error to cause
the Controller Fault Handler to execute. To do so, set the module property that
causes a major fault to result from an I/O connection error. The major fault
causes the execution of the Controller Fault Handler.
First, develop a routine in the Controller Fault Handler that can respond to I/O
connection faults. In the Module Properties dialog box of the I/O module or
parent communication module, check Major Fault On Controller If Connection
Fails While in Run Mode.
Figure 53 - I/O Connection Fault Causes Major Fault
For more information about programming the Controller Fault Handler, see the
Major, Minor, and I/O Faults Programming Manual, publication 1756-PM014
.
Parent Communication Module Properties
I/O Module Properties

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1769-L24ER-QB1B and is the answer not in the manual?

Allen-Bradley 1769-L24ER-QB1B Specifications

General IconGeneral
BrandAllen-Bradley
Model1769-L24ER-QB1B
CategoryController
LanguageEnglish

Related product manuals