EasyManuals Logo
Home>AUX>Air Conditioner>ANB66FVAMT

AUX ANB66FVAMT User Manual

AUX ANB66FVAMT
149 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #121 background imageLoading...
Page #121 background image
AUX-DC inverter ARV outdoor unit individual series technical manual
118
2. Commissioning procedure
2.1 Cooling Commissioning procedure
System confirmation
Indoor units confirmation
Outdoor units confirmation
Whether the subordinate unit can
work normally
Whether indoor unit blows air at normal
air speed, whether there is abnormal
noise in indoor and outdoor units
After the stable operation of the system (normal
operation last for 1 hour), write down the
operation parameters,
Whether there is something wrong with indoor
units, solve failures according to failure code.
Analysis the data according to parameters in table 1
After eliminating the problem, turn off the indoor unit one by
one to confirm whether the electric expansion valve of the
stand by indoor unit can be closed or not).
After stable operation (at last for 1 hour), write down operation
parameters as in table 1, and analysis the data.
Eliminate fault, system operation confirmed, refrigeration commissioning completed.
Make sure the outdoor unit canfind all the indoor units.
Start up all the indoor units in cooling mode with high fan speed
and setting temperature of 16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUX ANB66FVAMT and is the answer not in the manual?

AUX ANB66FVAMT Specifications

General IconGeneral
BrandAUX
ModelANB66FVAMT
CategoryAir Conditioner
LanguageEnglish

Related product manuals