AUX-DC inverter ARV outdoor unit individual series technical manual
127
Indoor unit temperature sensor is abnormal.
4.Outdoor unit error code explanation
4.1 Temperature or pressure sensor failure
Ambient temperature
sensor failure
1. Temperature sensor is broken.
2. Test temperature exceeds limit.
3. Sensor connection is incorrect.
4. Outdoor unit PCB failure.
Defrosting temperature
sensor failure
Discharge temperature of
inverter compressor failure
Suction temperature of
compressor failure
Temperature sensor of
inverter module failure
High pressure sensor
failure
1. High pressure sensor is broken.
2. Low pressure sensor connection is incorrect.
3. Outdoor unit PCB failure
Low pressure sensor
failure.
1. Low pressure sensor is broken.
2. The connection between sensor and outdoor PCB incorrect
3. Outdoor unit PCB failure
High pressure switch failure
1. The stop valve on high pressure side is not opened normally.
2. Outdoor fan motor is failed.
3. Outdoor heat exchanger is dirty.
4. In heating mode indoor fan stop
5. In heating mode indoor EXV can’t open normally.
Low pressure switchfailure
1. The stop valve on suction side is closed
2. In cooling mode indoor EXV is closed or blocked
3. In heating mode outdoor unit EXV is closed or blocked
4. In heating mode outdoor unit fan stop
5. In heating mode outdoor unit air outlet block