DC inverter ARV Individual Series technical manual
87
3.8Electric Characteristic
Model
Unit
Power supply
OFM
Hz
Voltage
(V)
MCA
(A)
MFA
(A)
Output power
(W)
FLA
(A)
ARV-H615/5R1B
50
380-415V
36.20
50
750*2
3.50
ARV-H670/5R1B
50
380-415V
41.90
50
750*2
3.50
ARV-H730/5R1B
50
380-415V
57.90
80
750*3
3.50
ARV-H780/5R1B
50
380-415V
58.86
80
750*3
3.50
ARV-H850/5R1B
50
380-415V
64.13
80
750*3
3.50
ARV-H900/5R1B
50
380-415V
65.28
80
750*3
3.50
Symbols:
MCA: Min. Circuit Amps. (A);
MFA: Max. Fuse Amps. (A);
OFM: Outdoor Fan Motor;
FLA: Full Load Amps. (A);
Note:
1. RLA is based on the following conditions, Indoor temp. 27°C DB/19°C WB, Outdoor temp. 35°C DB.
2. Maximum allowable voltage variation between phase and phase is 2%.
3. Selection wire size based on the larger value of MCA.
4. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).