4.3 Connecting the Syscompact 2000
Preparation of the DUT
Disconnect all poles of the DUT, prevent resetting, and ground DUT. Neighbouring parts
under voltage must be insulated. Check that the test voltage cannot lead to flashovers to
neighbouring parts under voltage. In a three- or more-phase-system ground all conductors
except the phase under test.
Connecting of safety earth
Connect the Syscompact 2000 with the included safety-earth-line (yellow-green) to the
safety-earth-connector (B) and to the to the station earth.
Use the foreseen clamps for this. For best possible earthing take care for a short connection
(minimum of cable length) between safety-earth-connector and station earth. ´Therefore
every three meter metal terminations are incorporated into the protection earth cable.