Product overview
BC8050 und BC815014 Version: 3.0.0
2.4.3 Technical Data - RS232
Fig.3: BC8150
System data RS232 (BC8150)
Protocols • Address 1-39 serial ADS, KS8000 protocol (automatic recognition of the
protocol and the baud rate (9600, 19200, 38400 baud, fixed data frame, 8
data bits, even parity, one stop bit)
• Address 40-59 ModbusRTU (fixed baud rate 1200, 2400, 4800, 9600,
19200, 38400, DEFAULT 9600 baud, 8 bit data, optionally even, odd, no
default no parity)
Number of I/O modules 1
Number of I/O points depending on controller
Data transfer medium shielded copper cable, 3 x 0.25 mm²
Segment length up to 15m
Data transfer rate 1200 - 38400baud
Topology RS232 peer to peer
Transmission time depending on protocol and baud rate