AMC2 Modular
Controller
Technical Data | en 59
Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |
7 Technical Data
Hardware
Integrated Microcontroller (32 bit, 30MHz)
SRAM (256kB)
Serial EEPROM
RTC (real time clock)
Pluggable Compact Flash card
Battery for SRAM and RTC
DIL switch for host settings (address and protocol mode)
Host interfaces
Ethernet 10/100Mbit/s
Four Wiegand interfaces for up to four card readers
(Output rating: 280 mA each @ 11.8-12Vdc)
Eight relay outputs
maximum ratings (wet and dry):
switching voltage: 30Vdc
switching current: 1,25A
operating ratings (dry):
1,25 A @ 30 Vdc
2 A @ 12 Vdc
1,5 A @ 24 Vdc
operating ratings (wet):
8.9-30 Vdc, 1.25 A
(voltage output is dependent on board voltage input)
Eight analog inputs with tamper detection; only connect dry
contacts
RS-485 extension interface:
Transfer rate: 9,6 kBit/s,
no parity, 8 bit, 2 stop bit
Tamper contact for external enclosures
RS-485 output power rated maximum 2.5 A @ 9.0-30 Vdc
(voltage output is dependant on board voltage input)
Power input
10 to 30 Vdc, max 3 A