• The cabling of the Ethernet wires may not leave the building.
•
Observe the bending radius of the cables used when routing the connecting lines.
• Use strain reliefs for all cables.
• Install the control only horizontally on a mounting rail attached to a wall.
• Keep the maximum distance possible from interference sources.
•
Provide the following minimum distances for sufficient cooling:
In case of a several line design, the supply air has to be measured under each line and its limit value
has to be observed. For information on ambient temperatures, refer to ⮫ Chapter 6.1 “Ambient
conditions of the ctrlX CORE” on page 12.
Fig. 9: Minimum distances for the circulation of ambient air
• Additionally, provide sufficient distance for mounting, dismounting, plugs and cables.
10.3 Mounting the control
NOTICE
Damage of the device by plug mounting under voltage!
− Before mounting or dismounting components, disconnect the control -
including its components - from voltage.
− Connect the voltage only after the control and its components have been
set up.
Mounting, dismounting and electric installation