ctrlX CORE
Ambient conditions of the ctrlX CORE
Bosch Rexroth AG
R911405645, Edition 05
6 Ambient conditions
6.1 Ambient conditions of the ctrlX CORE
Ambient temperature during operation Up to 2,000 m: -25 °C to +55 °C
2,000 m to 3,000 m: -25 °C to +50 °C
3,000 m to 4,000 m: -25 °C to +45 °C
4,000 m to 5,000 m: -25 °C to +40 °C
Ambient temperature during storage and transport -40 °C to +70 °C
Operating altitude acc. to DIN 60204 Up to 5,000 m above sea level
Permitted air humidity according to
DIN EN 61131-2
5% to 85%, no condensation
Protection class acc. to DIN EN 60 529 IP 20 (not evaluated by UL)
Protection class acc. to DIN EN 61010-2-201 III
Overvoltage category acc. to IEC 60664-1 2
Contamination level acc. to EN 61010-1 2, no condensation allowed
Mechanical tests
Vibration resistance acc. to DIN EN 60068-2-6
Oscillations, sinusoidal in all three axes
5 Hz - 8.4 Hz with 3.5 mm amplitude
8.4 Hz -150 Hz with 1 g peak acceleration
Shock test acc. to DIN EN 60068-2-27 Shock stress: Shock resistance in all three axes, 11
ms semi-sinusoidal 15 g
Broadband noise acc. to DIN EN 60068-2-64 5-20-150 Hz with 0.572 g, 5 h per axis
Electrostatic discharge
ESD resistance acc. to DIN EN 61131-2
Test voltage
Criterion B
8 kV for air discharge
4 kV for contact discharge
To avoid vibration, secure the cables at a short distance (< 20 cm).
NOTICE
Failure of the product due to contaminated air!
The ambient air must not contain acids, alkaline solutions, corrosive
agents, salts, metal vapors and other electrically conductive contami-
nants in high concentrations
The devices to be installed into the housing and installation compart-
ments must at least comply with the degree of protection IP 54
according to DIN EN 60529.
The device shall be provided in a suitable fire enclosure in the end-use
application.
NOTICE
Defective product due to gases jeopardizing functions
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide
(SO
2
) and hydrogen sulphide (H
2
S)). The product is not resistant against
these gases.

Table of Contents

Other manuals for Bosch Rexroth ctrlX CORE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Rexroth ctrlX CORE and is the answer not in the manual?

Bosch Rexroth ctrlX CORE Specifications

General IconGeneral
BrandBosch
ModelRexroth ctrlX CORE
CategoryController
LanguageEnglish

Related product manuals