4.0 Compressor Features and Accessories
25
4.1 06D Compressor Motor Protection
The 06D compressors, when purchased with overloads
installed in the compressor terminal box, are protected
from motor overcurrent and overtemperature. The
motor is completely protected against locked rotor, run-
ning overload, primary and secondary single phasing,
and loss of refrigerant conditions. These compressors
also comply with UL, CSA, and NEC(National Electrical
Code) requirements for inherent motor protection.
These compressors also comply with the "CE Mark"
requirements for European applications.
Primary Motor Protection
Texas Instruments supplementary overloads are nor-
mally supplied with 06D compressors. These relays trip
at or below the maximum continuous current(MCC) list-
ed in the electrical data tables. These current sensitive,
pilot duty relays are located inside the terminal box and
will automatically reset after tripping (See Table 5). Load
terminals of the overloads are 1/4 inch quick connect
for ratings of 30 amps and below, and #10 screw termi-
nals for ratings over 30 amps. Control circuit terminals
are 1/4 inch quick connects. See section 1.13 for wiring
recommendations.
ELECTRICAL DATA
COMPRESSOR MAX.
MODEL VOLT HP kW MCC RLA LRA
06DR1090GA31*0 575 4.4 2.8 21.3
GA32*0 208/230 2 3.1 12.1 7.8 53.3
GA36*0 460 5.5 3.5 26.3
06DR0130CA31*0 575 7.0 4.5 28.4
CA32*0 208/230
3 4.3
17.4 11.2 71.0
CA36*0 460 8.7 5.6 35.5
06DR3160CA31*0 575 10.8 6.9 40.0
CA32*0 208/230
5 6.25
27.0 17.3 100.0
CA36*0 460 13.5 8.6 50.0
06DR7180DA31*0 575 10.8 6.9 40.0
DA32*0 208/230
5 6.25
27.0 17.3 100.0
DA36*0 460 13.5 8.6 50.0
06DR8200DA31*0 575 17.6 11.3 64.0
DA32*0 208/230 6.5 9.8 44.0 28.2 160.0
DA36*0 460 22.0 14.1 80.0
06DR7250DA31*0 575 17.6 11.3 64.0
DA32*0 208/230 6.5 9.8 44.0 28.2 160.0
DA36*0 460 22.0 14.1 80.0
06DR2280DA31*0 575 22.2 14.2 79.0
DA32*0 208/230 7.5 12.8 55.5 35.6 198.0
DA36*0 460 27.8 17.8 99.0
06DR3370DA31*0 575 25.0 16.0 91.0
DA32*0 208/230 10 16.5 62.0 39.7 228.0
DA36*0 460 31.0 19.9 114.0
ELECTRICAL DATA
COMPRESSOR MAX.
MODEL VOLT HP kW MCC RLA LRA
06DM8080GA31*0 575 7.0 4.5 28.4
GA32*0 208/230
3 4.1
17.4 11.2 71.0
GA36*0 460 8.7 5.6 35.5
06DM3130CA31*0 575 10.8 6.9 40.0
CA32*0 208/230
5 6.25
27.0 17.3 100.0
CA36*0 460 13.5 8.6 50.0
06DM3160CA31*0 575 10.8 6.9 40.0
CA32*0 208/230
5 6.25
27.0 17.3 100.0
CA36*0 460 13.5 8.6 50.0
06DM3370DA31*0 575 25.0 16.0 91.0
DA32*0 208/230 10 16.5 62.0 39.7 228.0
DA36*0 460 31.0 19.9 114.0
06DA8182AA31*0 575 17.6 11.3 64.0
AA32*0 208/230 6.5 9.8 44.0 28.2 160.0
AA36*0 460 22.0 14.1 80.0
06DA8252BA31*0 575 22.2 14.2 79.0
BA32*0 208/230 7.5 12.8 55.5 35.6 198.0
BA36*0 460 27.8 17.8 99.0
06DA3282BA31*0 575-3-60 25.0 16.0 91.0
BA32*0 208/230 10 16.5 62.0 39.7 228.0
BA36*0 460 31.0 19.9 114.0
06DA537BA01*0 575 32.0 20.5 96.0
BA12*0 208/230 15 20.7 89.0 57.1 266.0
BA06*0 460 40.0 25.6 120.0
ALLOWABLE OPERATING RANGE
NOMINAL VOLTAGE MAXIMUM MINIMUM
208/230 254 187
460 529 414
575 661 518
400 (50Hz) 460 342
200 (50Hz) 230 180
* 0 or 5.
* 0 or 5.
LEGEND
LRA — Locked Rotor Amps
MCC — Maximum Continuous Current
RLA — Rated Load Amps