nal
ON/OFF
HTG/CLG
Terminal Block NX Version
4.1.1 Sanitary hot water
The 30AWH units drive a 3-way valve (7) to manage a sanitary water
accumulation tank. The operating logic provides that, in the case of
a request for sanitary water by an accumulation tank (8), the system
controls a 3-way valve to direct the hot water only to the tank and to
operate at the maximum capacity to provide water at 60 °C (compatible
with the operating envelope).
Procedure to install a three way valve:
1. Install three way valve on water piping closer as possible to
AQUASNAP
2. Connect electrically three way valve to N, 18, 10 terminals (1,2 and
QJOTJO/9WFSTJPOJODBTFPGUISFFXBZWBMWFXJUITQSJOHSFUVSO
only connect N and 10 terminals
8
9
7
3. Connect Sanitary Hot Water dry contact thermostat/request (eg.
45°C ON, 55°C OFF) to 13 and 15 terminals (7 and 8 in NX version)
Closing that contact, GMC drives three way valve and AQUASNAP runs
BU¡$JOIFBUJOHNPEFUPPCUBJOIPUXBUFSQSJPSJUZ4)8XIFO
contact opens, GMC drives back the system in the previous mode
DPPMJOHIFBUJOHPSPò
Attention:
1) The sanitary water request has higher priority than the
programmed operating mode in both heating and cooling mode.
2) NUI code 146 congure SHW logic when Aquasnap unit is in OFF
mode.
SM_30AW.indd 23 14-03-2011 14:42:06