Ensure that the AC-input power supply module has a detachable power cord.
Each chassis power supply should have a separate, dedicated branch circuit.
North America
C9400-PWR-3200AC only—Power supply modules require a 20 A circuit.
C9400-PWR-2100AC only—Power supply modules require a 15 A circuit.
International—Circuits should be sized according to local and national codes.
If you are using a 208 or 240 VAC power source in North America, note that such lines are considered
hot and the circuit must be protected by a two-pole circuit breaker.
This product relies on the building's installation for short-circuit (overcurrent)
protection. Ensure that the protective device is rated not greater than these values
for the U.S. and EU:
20 A circuit breaker for an AC-input power supply module.
50 A DC-rated circuit breaker for each input of a DC-input power supply
module, for safety purposes - irrespective of whether the inputs are power
from a single or separate DC sources.
Statement 1005
Warning
This product requires short-circuit (overcurrent) protection, to be provided as
part of the building installation. Install only in accordance with national and local
wiring regulations. Statement 1045
Warning
A readily accessible two-poled disconnect device must be incorporated in the
fixed wiring. Statement 1022
Warning
The source AC outlet must be within 9.84 to 14 feet (3.0 to 4.293 meters) of the system - depending on
the length of the power cord, and should be easily accessible.
The AC power receptacles used to plug in the chassis must be the grounding type. The grounding
conductors that connect to the receptacles should connect to protective earth ground at the service
equipment level.
Power Connection Guidelines for DC-Powered Systems
When connecting DC-input power supply modules to the site power source, observe the guidelines described
here.
Cisco Catalyst 9400 Series Switches Hardware Installation Guide
37
Preparing for Installation
Power Connection Guidelines for DC-Powered Systems

Table of Contents

Other manuals for Cisco Catalyst 9400 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco Catalyst 9400 Series and is the answer not in the manual?

Cisco Catalyst 9400 Series Specifications

General IconGeneral
BrandCisco
ModelCatalyst 9400 Series
CategorySwitch
LanguageEnglish

Related product manuals