Statement 1002—DC Power Supply
When stranded wiring is required, use approved wiring terminations, such as closed-loop or spade-type
with upturned lugs. These terminations should be the appropriate size for the wires and should clamp both
the insulation and conductor.
Warning
Statement 1003—DC Power Disconnection
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Warning
Statement 1005—Circuit Breaker
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that the
protective device is rated not great than: AC power 120VAC, 20A (US), 240VAC, 16A (EU), DC power
60V, 35A.
Warning
Statement 1022—Disconnect Device
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring.
Warning
Statement 1025—Use Copper Conductors Only
Use copper conductors only.
Warning
Statement 1028—More Than One Power Supply
This unit might have more than one power supply connection. All connections must be removed to
de-energize the unit.
Warning
Statement 1030—Equipment Installation
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Warning
Statement 1040—Product Disposal
Ultimate disposal of this product should be handled according to all national laws and regulations.
Warning
Statement 1045—Short-circuit Protection
This product requires short-circuit (overcurrent) protection to be provided as part of the building installation.
Install only in accordance with national and local wiring regulations.
Warning
Cisco Firepower 4100 Series Hardware Installation Guide
66
Maintenance and Upgrades
Remove and Replace the Power Supply Module