IGS-NT Communication Guide
102
7.4.10 Reset/Confirm Alarm
Request: 01 10 18 D6 00 03 06 08 F7 00 00 00 01 49 CB
01 = controller address
10 = Modbus command
18D6
= Register address: Object for engine commands
(46359) – 40001 = 6358 DEC => 18D6 HEX
00 03 = number of Modbus registers
06 = data length in bytes (08F70000+0001)
08F70000
= argument for Fault reset (Commands for IGS-NT
(page 72))
0001
= command number (Commands for IGS-NT (page
72))
CB 49
= Check field calculation (page 143) (write LSB MSB
!)
Response: 01,10,18,D6,00,03,67,50
01 = Controller address
10 = Modbus command
18 D6 = Register addres
00 03 = Release value, number of written Modbus registers
50 67 = Check field calculation (page 143)