IGS-NT Communication Guide
127
10. Navigation window will appear:
11. For each write-type parameter modify the property Update mode to triggered mode and define trigger byte
address. The Profibus master must update the parameter data field first and then increase the trigger byte
value to write the parameter (register) to the controller.
12. Write the configuration to the P485 and save it also to disk as backup.
8.7.4 Controller settings
IG/IS-NT
Comms settings: RS232(1) mode / RS232(2) mode* ODBUS-DIRECT
Comms settings: RS232(1)MBCSpd / RS232(2)MBCSpd* according to converter setting
Comms settings: RS485(1)conv. / RS485(2)conv.* according the converter setting
Note:
* Second RS232/485 port available only in IG-NTC/EEC and IS-NT.