IGS-NT Communication Guide
142
Example
Example Register Protection#2 Protection#1
45754 Warning 7 Warning 8
45755 Warning 9 Warning10
45756 SD 11 SD 12
45863 Oil press Water temp
45864 Fuel level N/A
45925 BIN 1 BIN 2
45926 BIN 3 BIN 4
Register number 45863 carries informations about states of protections Oil press and Water temp. For
undersanding of particular bit meaning use previous register map according table bellow. The first line contains
numbers of bits of the registers, the second one contains values of particullar bits. Vallues of particullar sections
are in third line, their meaninng is in the last line.
Level 1 = yelow level in protection settings
Level 2 = red level in protection settings
Protection#2 = Oil press Protection#1 = Water temp
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 1 1 0 0 1 1 0 0 1 0 0 0 0 1 0
1 4 6 1 0 2
Sensor failure active,
confirmed (or not
configured as
protection)
Level 2
previously
active, not
confirmed yet
Level 1 active,
not confirmed
yet
Sensor
failure
active,
confirmed
Level 2
inactive
Level 1 active,
confirmed
Meaning of particular bits
Bit Value of bit = 0 Value of bit = 1
0,3,8,11
protection is not blocked, if the condition for activation is
fulfilled protection can be announced
the condition for activation of
protection is fulfilled but protection
is blocked
1,4,9,12
protection is not active (condition for activation is not
fulfilled)
protection is active (condition for
activation is fulfilled)
2,5,10,13
protection has not been announced (the protection is not
active or is active but blocked or it was active previously
and was confirmed)
protection has been announced (is
active and not blocked and was not
confirmed)