5 | Operation
User reference guide
34
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620245-1 – 2020.06
▪ Initially, the DHW tank temperature is the same as the temperature of the
domestic water entering the DHWtank (example: 15°C).
▪ At 00:00 the DHW tank is programmed to heat up the water to a preset value
(example: Comfort = 60°C).
▪ During the morning, you consume hot water and the DHW tank temperature
decreases.
▪ At 14:00 the DHW tank is programmed to heat up the water to a preset value
(example: Eco = 50°C). Hot water is available again.
▪ During the afternoon and evening, you consume hot water again and the
DHWtank temperature decreases again.
▪ At 00:00 the next day, the cycle repeats.
5.7.4 Scheduled + reheat mode
In scheduled + reheat mode, the domestic hot water control is the same as in
scheduled mode. However, when the DHWtank temperature drops below a preset
value (=reheat tank temperature – hysteresis value; example: 35°C), the DHWtank
heats up until it reaches the reheat set point (example: 45°C). This ensures that a
minimum amount of hot water is available at all times.
Example:
t
T
t
60°C
00:00 07:00
50°C
45°C
15°C
14:00 21:00
35°C
1
2
4
5
3
T
t
Domestic hot water tank temperature
t Time
5.7.5 To change the domestic hot water temperature
In Reheat only mode, you can use the tank temperature setpoint screen to read
out and adjust the domestic hot water temperature.
1 Go to [5]: Tank.
2 Adjust the domestic hot water temperature.
a Actual domestic hot water temperature
b Desired domestic hot water temperature