EasyManuals Logo

Daikin FTXS35K2V1B Service Manual

Daikin FTXS35K2V1B
267 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #207 background imageLoading...
Page #207 background image
SiBE121123_A Troubleshooting for Outdoor Unit
Service Diagnosis 196
7.13 Position Sensor Abnormality
Error Code
H6
Method of Error
Detection
A compressor startup failure is detected by checking the compressor running condition through
the position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Disconnection of the compressor relay cable
Defective compressor
Defective outdoor unit PCB
Startup failure caused by the closed stop valve
Input voltage outside the specified range

Table of Contents

Other manuals for Daikin FTXS35K2V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTXS35K2V1B and is the answer not in the manual?

Daikin FTXS35K2V1B Specifications

General IconGeneral
BrandDaikin
ModelFTXS35K2V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals