SiBE121123_A Forced Cooling Operation
Trial Operation and Field Settings 220
2. Forced Cooling Operation
Ex: Wall mounted type FTXS-J Series
Item Forced Cooling
Conditions The forced cooling operation is allowed when both the following conditions
are met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
for 5 seconds.
Operating room All rooms
Command frequency 40 class: 70 Hz
50 class: 47 Hz
End The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor
unit again.
Others The protection functions are prior to all others in the forced cooling
operation.
(R14226)
[ON/OFF] button (SW1)